Brand Name: hiseer
Model Number: AW13/B
Place of Origin: Guangdong, China (Mainland)
Hiseer’s high efficiency chiller are well designed for high efficiency running, brings quiet consistent comfort to thousands of people around the world.
Compact design with operational built-in auxiliary electric heater and hot water pump.
Built-in differential pressure flow switch protect the unit from insufficient water flow rate.
Hitachi scroll R410A compressor
With Germany’s Siemens controller, the control system is intelligent ,stable and durable to assure safe running .
SWEP/GEA Brazed Plate Heat Exchanger (BPHE) is one of the most efficient ways to transfer heat from refrigerant to water. A BPHE consists of corrugated plates combined to create complex channels through which refrigerant and water can be distributed.
Hiseer’s air cooled chiller with built-in de icing heater at
the bottom ,free of ice on the bottom in winter.
The compressor is well insulated to reduce noise
Two speed fan are designed for quite operation.
Technical data:
Air cooled chiller | AW10/B | |||
Heat output/Power consumption at 7/35°C | kW | 11.0/2.7 | ||
COP at 7/35°C | 4.07 | |||
Heat output/Power consumption at 7/45°C | kW | 10.5/3.3 | ||
COP at 7/45°C | 3.18 | |||
Heat output/Power consumption at 7/55°C | kW | 10.2/4.1 | ||
COP at 7/55°C | 2.49 | |||
Heat output/Power consumption at 2/35°C | kW | 9.5/2.6 | ||
COP at 2/35°C | 3.65 | |||
Heat output/Power consumption at 2/45°C | kW | 9.2/3.4 | ||
COP at 2/45°C | 2.71 | |||
Heat output/Power consumption at -7/35°C | kW | 7.2/2.3 | ||
COP at -7/35°C | 3.13 | |||
Heat output/Power consumption at -7/45°C | kW | 7.1/3.4 | ||
COP at -7/45°C | 2.09 | |||
Cool output/Power consumption at 35/7°C | KW | 9.5/3.3 | ||
COP at 35/7°C | 2.88 | |||
Starting current | A | 46 | ||
Soft-start relay | ||||
Power | 380-415V/3PH/50Hz | |||
Compressor | HITACHI scroll | |||
Condenser | Brazed plate heat exchanger | |||
Nominal flow heating medium | m3/h | 1.87 | ||
Internal pressure drop at nominal flow | kPa | 23 | ||
Air flow | m3/h | 3000 | ||
Nominal output fan | W | 220 | ||
Max outgoing heating medium temperature | °C | 55°C | ||
Refrigerant R410A filling weight | kg | 3.8 | ||
Dimensions(HxWxD) | mm | 1050x1050x450 | ||
Pipe connector | DN25 | |||
Weight | kg | 125 | ||
Operating ambient temp. range | °C | Heating -10~35 | ||
Cooling 10~45 | ||||
DHW -10~43 | ||||
The above data is tested by EN14511. 7/35°C means air temp. 7°C,outlet water temp. 35°C |
typical installation diagram: