- Products Details
Quick Details
-
Brand Name: Soloon
Model Number: S6061SF-10DF/220V
Place of Origin: Beijing, China
Packaging & Delivery
- Packaging Details: Paper carton with pallet
- Delivery Detail: Within two weeks after receving the payment
Specifications
S6061SF-10/15 series fire smoke damper actuator
Summary:
The S6061SF-10/15Nm fire smoke damper actuators are designed specifically for application in the HVAC and light industrial markets. By the change of input signal, the actuator can be controlled at any point. It can supply a feedback signal of 0-10V, after cut the power, the actuator can return by the spring.
Features:
l Control by 2/3 point or 0…10V
l Shaft size up to 12* 12mm
l Two fixed auxiliary switches available
l On/off type with manual function
l Using fixed, compact and anti-impact steel shell
l With IP54 standard
Technical datasheet:
Item |
S6061SF- 10DF(S)/24V |
S6061SF- 10DF(S)/230V |
S6061SF- 10AF/24V |
S6061SF- 15DF(S)/24V |
S6061SF- 15DF(S)/230V |
S6061SF-15AF/24V |
||||
Torque |
10Nm |
15Nm |
||||||||
Damper area |
2m2 |
3m2 |
||||||||
Power supply |
24VAC/DC 50/60Hz |
230VAC 50/60Hz |
24VAC/DC |
|||||||
Operating Power Consumption |
5W |
6W |
||||||||
At end stops Power Consumption |
2.5W |
2.5W |
||||||||
Wire size |
10VA |
7VA |
10VA |
7VA |
||||||
Connection cable |
D type power:1m cable 2*0.75 m2 A type power:1m cable 4*0.5 m2 |
|||||||||
Auxiliary switch (F):1m cable 6*0.5 m2 |
||||||||||
Thermal sensor(S):1m cable 2*0.5 m2 |
||||||||||
Control signal |
On/off |
0~10V |
On/off |
0~10V |
||||||
Running time |
motor≤100S;spring return≤20S |
motor≤130S;spring return≤20S |
||||||||
Rotation angle |
0~90°(Max 93º) |
|||||||||
Indicate |
Mechanical indicator |
|||||||||
Weight |
2.6Kg |
|||||||||
Life cycle |
70000 |
|||||||||
Noise |
50dB(A) and 62dB(A) |
|||||||||
Electric level |
Ⅲ |
Ⅱ |
Ⅲ |
Ⅲ |
Ⅱ |
Ⅲ |
||||
IP protection |
IP54 |
|||||||||
Temperature |
-20~+50℃ |
|||||||||
Humidity |
5~95%RH |
|||||||||
Standard |
CE & UL |
|||||||||
Note:The on/off type can match 72°C thermal sensor and modulating without manual function.
Notice: manual operation instruction
Insert the hand handle into the hex hole, smoothly and slowly turn around the handle by clockwise (or counter clockwise) rotation, according to the diagram of the product label. At the same time, the outputshaft will follow and turn by clockwise (or counter clockwise) rotation. When the outputshaft moves to the required position, then turn the handle conversely by counter clockwise rapidly (or clockwise) with 90 ℃,(Should not use the manual lock while the turbine springs is bouncing back, otherwise, the fast reversing standstill locking part could bumps into the springs. And the result of manual lock-on system would be malfunctioned.)meanwhile the outputshaft will be blocked. Then turn slightly the handle by another clockwise (or counter clockwise), the outputshaft will move again.
[Attention]:Please do not operate manually when the actuator is speedly rebounding, otherwise it causes easily unlocking by manual or assembly damage.
Scale: --
Country/Region: China (Mainland)/Asia
Established: 2001