- Products Details
Quick Details
-
Brand Name: Hengsen
Model Number: DF/F-05
Place of Origin: China
Packaging & Delivery
- Packaging Details: 1
- Delivery Detail: 1
Specifications
Product introduction
The DF/F-05 series screw cast brass valves can adjust the flow of cold/hot water after it is matched with the controller equipment of DF/Q motor actuator. It is available for the liquid control system such as the central air-conditioner, heating, water disposal, industry processing and so on.
Features
●The seal parts of valve stem: NBR seal parts of four-layer V type or O type group
●Valve stem: stainless steel 1Cr18Ni9Ti
●Valve core: brass or 1Cr18Ni9Ti
●Bearing: 1.6MPa
●Work medium: water, flow temperature: -10~95℃
●Flow feature: less than 0.05% of KV
Installation and maintenance
- That valve stem running up means that valve is closing.
- Make sure the pipe is cleat before installation.
- It must be at the same point when the pipe and valve body are connected, the flow direction should be same as the direction of the label.
- When the actuator is installed on the valve vertically, it should be above the valve to leave enough space for daily maintenance.
●When maintenance, the electricity should be cut off and there is no pressure in the water system
Specification and technical data
Type
|
Caliber (mm) |
Model
|
Coefficient(KV) |
Max. pressure(MPa)) |
Valve journey stem |
||
05A(B) |
05C |
DF/Q-J |
DF/Q-H |
||||
DF/F-05A(B﹑C)-2015-JC(HC) |
DN |
2-way |
3.1 |
2.5 |
0.6 |
0.6 |
15 |
DF/F-05A(B﹑C)-3015-JC(HC) |
DN |
3-way |
3.1 |
2.5 |
0.6 |
0.6 |
15 |
DF/F-05A(B﹑C)-2020-JC(HC) |
DN |
2-way |
5 |
3.7 |
0.6 |
0.6 |
15 |
DF/F-05A(B﹑C)-3020-JC(HC) |
DN |
3-way |
5 |
3.7 |
0.6 |
0.6 |
15 |
DF/F-05A(B﹑C)-2025-JC(HC) |
DN |
2-way |
7.4 |
5.3 |
0.6 |
0.6 |
20 |
DF/F-05A(B﹑C)-3025-JC(HC) |
DN |
3-way |
7.4 |
5.3 |
0.6 |
0.6 |
20 |
DF/F-05A(B﹑C)-2032-JC(HC) |
DN |
2-way |
11.5 |
9.5 |
0.6 |
0.6 |
20 |
DF/F-05A(B﹑C)-3032-JC(HC) |
DN |
3-way |
11.5 |
9.5 |
0.6 |
0.6 |
20 |
DF/F-05A(B﹑C)-2040-JC(HC) |
DN |
2-way |
14 |
11 |
0.6 |
0.6 |
20 |
DF/F-05A(B﹑C)-3040-JC(HC) |
DN |
3-way |
14 |
11 |
0.6 |
0.6 |
20 |
DF/F-05A(B﹑C)-2050-JC(HC) |
DN |
2-way |
17 |
16 |
0.6 |
0.6 |
20 |
DF/F-05A(B﹑C)-3050-JC(HC) |
DN |
3-way |
17 |
16 |
0.6 |
0.6 |
20 |
DF/F-05A(B)-2065-JC(HC) |
DN |
2-way |
63 |
|
0.25 |
0.3 |
20 |
DF/F-05A(B)-3065-JC(HC) |
DN |
3-way |
63 |
|
0.25 |
0.3 |
20 |
DF/F-05A(B)-2080-JC(HC) |
DN |
2-way |
78 |
|
0.20 |
0.25 |
20 |
DF/F-05A(B)-3080-JC(HC) |
DN |
3-way |
78 |
|
0.20 |
0.25 |
20 |
Notice: The data in the chart is recommendatory. You can equip other actuator of the same system junction after suggesting the technicians.
Outline size
Type |
Connecting thread |
Size(mm) |
Weight (Kg) |
|||
A |
B |
C |
||||
JC |
HC |
|||||
DF/F-05A(B﹑C)-2015-JC(HC) |
G1/2 |
84 |
41 |
130 |
119 |
2.2 |
DF/F-05A(B﹑C)-3015-JC(HC) |
G1/2 |
84 |
53 |
130 |
119 |
2.4 |
DF/F-05A(B﹑C)-2020-JC(HC) |
G3/4 |
84 |
41 |
130 |
119 |
2.3 |
DF/F-05A(B﹑C)-3020-JC(HC) |
G3/4 |
84 |
53 |
130 |
119 |
2.5 |
DF/F-05A(B﹑C)-2025-JC(HC) |
G1 |
104 |
52.5 |
135.5 |
124 |
3.5 |
DF/F-05A(B﹑C)-3025-JC(HC) |
G 1 |
104 |
64.5 |
135.5 |
124 |
3.8 |
DF/F-05A(B﹑C)-2032-JC(HC) |
G 1-1/4 |
110 |
57.5 |
138 |
127 |
3.7 |
DF/F-05A(B﹑C)-3032-JC(HC) |
G 1-1/4 |
110 |
65.5 |
138 |
127 |
4.2 |
DF/F-05A(B﹑C)-2040-JC(HC) |
G 1-1/2 |
120 |
63 |
140.5 |
129.5 |
4.4 |
DF/F-05A(B﹑C)-3040-JC(HC) |
G 1-1/2 |
120 |
76 |
140.5 |
129.5 |
5.0 |
DF/F-05A(B﹑C)-2050-JC(HC) |
G 2 |
145 |
62.5 |
145 |
134 |
5.7 |
DF/F-05A(B﹑C)-3050-JC(HC) |
G 2 |
145 |
77.5 |
145 |
134 |
6.7 |
DF/F-05A(B)-2065-JC(HC) |
G 2-1/2 |
160 |
75 |
152.5 |
141.5 |
8.5 |
DF/F-05A(B)-3065-JC(HC) |
G 2-1/2 |
160 |
91 |
152.5 |
141.5 |
9.5 |
DF/F-05A(B)-2080-JC(HC) |
G 3 |
180 |
85 |
158.5 |
147.5 |
9.5 |
DF/F-05A(B)-3080-JC(HC) |
G 3 |
180 |
98.5 |
158.5 |
147.5 |
10.5 |
Scale: 301 - 500 People