Soft Starter Description
ZJR2 series soft starter can work with three-phase ,AC squirrel cage induction asynchronous motor ,The voltage is 320V~460V, 50HZ/60HZ and the current is 1200A and below .
ZJR2 series soft starter are in the process of motor starting and running a perfect protection function, adopted the closed loop control, greatly improving the stationarity of soft starting torque of the motor
The soft starter is a device type .It’s necessary to add breakers (short-circuit protection ) and AC contactor (Bypass) inside the cabinet . together with switches are made up of electric motor control circuit .
Main Features for ZJR2 series soft starter
1. 16 SCM control, intelligent all-digital display;
2. can be put into practice a soft starter control multiple motors;
3. Starting modes: Current limiting starter, Voltage ramp start , Kick start +current-limiting start, kick start +voltage ramp start . Current ramp start . Voltage current-limiting double closed –loop start .
4. free stop and soft stop , The stop time from 0 to 60 seconds can be arbitrary choosed .
5. Over current , Overload , Open phase, instantaneous stop and other fault protection .
with the flow, over loading, lack phase, instantaneous stop, and other malfunction protection;
6. Easy installation, simple operation, strong function and reasonable prices;
Technical Indications
Item |
Item Description |
||
Input Power Supply |
Input Voltage |
Three Phase 380V-15% ~ 415+10% |
|
Frequency |
50/60Hz |
||
Adaptive Motor |
Squirrel-cage three-phase asynchronous motor |
||
Starting Times |
It is recommended not to exceed 20 times per hour. |
||
Control Mode |
1) Operation panel control; 2) Operation panel + external control; 3) External control; 4) External control + COM control; 5) Operation panel + external + COM control; 6) Operation panel + COM control; 7) COM control; 8) No start or stop operation. |
||
Start Mode |
1) Current-limiting start; 2) Voltage ramp start; 3) Kick start + current-limiting start; 4) Kick start + voltage ramp start; 5) Current ramp start; 6) Voltage current-limiting double closed-loop start. |
||
Stop Mode |
1) Soft stop; 2) Free stop. |
||
Protective Function |
1) Open loop protection for external instantaneous stop terminals; 2) Over-heat protection for soft starter; 3) Protection for too long starting time; 4) Input open phase protection; 5) Output open phase protection; 6) Unbalanced three-phase protection; 7) starting over current protection; 8) Running overload protection; 9) Under voltage protection for power voltage; 10) Over voltage protection for power voltage; 11) Protection for fault parameter setting; 12) Load short circuit protection; 13) Auto restart or incorrect wiring protection; 14) Incorrect wiring protection of external control stop terminals. |
||
Ambient |
Place to be used |
Indoor location with good ventilation free from corrosive gas and conductive dust. |
|
Altitude |
Below 3000M. It have to rise the rate power when the altitude is more than 3000M. |
||
Ambient Temperature |
-30~+55℃ |
||
Ambient Humidity |
≤90%RH without dew condensation. |
||
Vibration |
<0.5G |
||
Structure |
Protection Class |
IP20 |
|
Cooling Pattern |
Natural wind cooling. |
Guide Model for ZJR2 Soft Starter(75kW-600kW )
Model |
Rated Power(KW) |
Rated Current (A) |
Outline Size |
Install Size |
Net Weight |
||||
H1 |
W1 |
D |
H2 |
W2 |
d |
||||
ZJR2-3750/4750 |
75 |
150 |
530 |
260 |
202 |
380 |
196 |
M8 |
<25 |
ZJR2-3900/4900 |
90 |
180 |
530 |
260 |
202 |
380 |
196 |
M8 |
<25 |
ZJR2-31150/41150 |
115 |
230 |
530 |
260 |
202 |
380 |
196 |
M8 |
<25 |
ZJR2-31320/41320 |
132 |
264 |
530 |
260 |
202 |
380 |
196 |
M8 |
<25 |
ZJR2-31600/41600 |
160 |
320 |
530 |
260 |
202 |
380 |
196 |
M8 |
<25 |
ZJR2-31850/41850 |
185 |
370 |
530 |
260 |
202 |
380 |
196 |
M8 |
<25 |
ZJR2-32000/42000 |
200 |
400 |
530 |
260 |
202 |
380 |
196 |
M8 |
<25 |
ZJR2-32500//42500 |
250 |
500 |
580 |
290 |
245 |
460 |
260 |
M8 |
<35 |
ZJR2-32800/42800 |
280 |
560 |
580 |
290 |
245 |
460 |
260 |
M8 |
<35 |
ZJR2-33200/43200 |
320 |
640 |
580 |
290 |
245 |
460 |
260 |
M8 |
<35 |
ZJR2-34000/44000 |
400 |
800 |
630 |
330 |
245 |
500 |
265 |
M8 |
<40 |
ZJR2-34500/44500 |
450 |
900 |
630 |
330 |
245 |
500 |
265 |
M8 |
<40 |
ZJR2-35000/45000 |
500 |
1000 |
760 |
406 |
260 |
540 |
370 |
M8 |
<45 |
ZJR2-36000/46000 |
600 |
1200 |
760 |
406 |
260 |
540 |
370 |
M8 |
<45 |
CHZIRI Soft Starter wiring diagram