Fresh Air System Controller Instruction
KF-900A
Description
The 900A Ventilation System intelligent controller features touch-button technology for flexible operation. The built-in NDIR sensor of the controller can monitor the indoor temperature, humidity and CO2 concentration in real time, and the controller output signal directly controls the start and rotation speed of the fresh air device. It is used in residential, commercial and industrial applications and it is effective in improving air quality.
Create a healthy, comfortable, efficient, environmentally friendly, energy-saving living and working environment.
Features
Operating mode: Auto, Manual, Programming
Wind speed : High, Med, Low and Auto speed
Programming setting different wind speeds
Time display
Manual bypass valve control
RS485 communication (optional)
Humidity display
Temperature display
LCD Display
Instruction
1. ON/OFF Controller: Press button to power ON / OFF. All Outputs and LCD will be closed in OFF state.
2.Switch the working mode: Press button to switch working mode. "Auto mode-→Manual-→Programming-→Auto mode"
3.Manual Mode: Manual Set the speed of Fan ( HIGH, MED, LOW or OFF) by button, and the Fan will run according to the setting. In this model, controller will not affected by CO2 concentration and timing.
4.Programming mode: Controlller will be run according to the set time & speed(7 days, 4 time periods each day).
5.Auto mode setting Concentration: In Auto mode, Long press button for 2 second, and then enter CO2 concentration value setting interface.It will appear CO2 concentration setting value and flash. Then Press and to adjust value(350-1000ppm) In Auto mode, Long press button for 2 second, and then enter PM2.5 concentration value setting interface.It will appear PM2.5 concentration setting value and flash. Then Press and to adjust value. Controller will be return to normal working mode and save setting Parameter automatically If there is no any operation for the buttons for 10 seconds during the setting process.
6.Auto mode:Controller will be adjusted speed by auto according to the air quality(pm2.5 and CO2 concentration)
PM2.5 concentration >70ug/m(setting Value) or CO2 concentration>500ppm(setting Value),Fan is in HIGH Speed State.
PM2.5 concentration >35-69ug/m3(setting Value range) or CO2 concentration>200-499ppm(setting Value range),Fan is in MED Speed State.
PM2.5 concentration >0-34ug/m3(setting Value range) or CO2 concentration>0-199ppm(setting Value range),Fan is in LOW Speed State.
PM2.5 concentration< setting value or CO2 concentration < setting value. Fan Stop working.
7.Programming Setting: Long press button for 2 second and then enter setting parameter interface. Firstly, local time calibration. Press button to change Week / Hour / Minute,and the corresponding parameter will flash.Press and button to adjust the value. After finsh Local time calibration, go on press button enter first period hour setting on Monday, press button change to Hour, Minute,Fan Speed and press and button adjust value. After done first period, press button enter second period hour setting on Monday...Repeat above steps to set all 28 time periods.Controller will be return to normal working mode and save setting Parameter automatically If there is no any operation for the buttons for 10 seconds during the setting process.
Parameter
Power supply: 200~240VAC,50Hz-60Hz
CO2 display range: 400ppm-1999ppm
CO2 adjustment range: 350-1000PPM
CO2 control range: 350~1500PPM
CO2 measurement maximum: 1999PPM
pm2.5 display range (option) : 1ug/m3-999ug/m3
Temp. display range: 0~50℃
Working Temp.: -10-50℃
Humidity range: 5~99%RH
Control power: ≤200W
Rated Power: < 2W
Pre-heat: 1 minute
output interface: 0-10V
Dimensions(W × H × D): 86×86×50MM
Wiring: 2 x 1.5 or 1 x 2.5MM2
Install hole spacing: 60mm
Protection Class: 30IP
Flame retardant rating: V0
Wiring Diagram
Terminal 1: Neutral
Terminal 2: Line
Terminal 3: High Speed Output
Terminal 4: Med Speed Output
Terminal 5: Low Speed Output
Terminal 6: Valve OFF
Terminal 7: Valve ON
Terminal 8 ,9: RS 485 ,Modbus RTU