Brand Name: Danfoss
Model Number: ICAD600-900,ICAD1200A-027H9122
Place of Origin: Denmark
ICAD600-900,ICAD1200A-027H9122 Danfoss actuators product description
Actuator types ICAD 600A and 1200A are
dedicated for use with ICM motor operated
valves. There are only two sizes of ICAD actuators
that cover the range of valves from ICM 20 to
ICM 150.
The ICAD is controlled via a modulating analogue
signal (e.g. 4 – 20 mA / 2 – 10 V) or a digital ON /
OFF signal. ICAD incorporates an advanced MMI
(Man Machine Interface), including continuous
display of Opening Degree, which gives the user
a very advanced and flexible setup procedure
that can meet many different applications.
ICAD600-900,ICAD1200A-027H9122 Danfoss actuators product Features
• Designed for industrial refrigeration
installations.
• Advanced and high speed Digital Stepper
Motor Technology
• Seven segment LCD display and three
programming keys included
• Valve opening degree can be observed
continuously.
• Can easily be configured to different
applications on-site (change speed, ON / OFF,
Fail Safe operation, modulating valve, etc..)
• Open – Close time: 3 – 45 seconds depending
on valve size
• Modulating, ON / OFF operation or Neutral
zone / 3 point control
• Multiple speed selection during operation
• Logging of old alarms
• Password protection
• Control input signal :
4 – 20 mA, 0 – 20 mA, 0 – 10 V, 2 – 10 V.
One or two digital inputs.
• Position feed back : 0 – 20 mA, 4 – 20 mA (ICM)
• 3 Digital ON / OFF feedback
• Resolution: 20 micron / step
(0.02 mm stroke pr. step)
• Total steps: 250 – 3650 depending on size
• Auto Calibration, Neutral zone
• In the event of a power failure, multiple fail safe
options are possible. During power failure, ICM
can be selected to:
Close ICM,
Open ICM,
Stay in the same position, as when power
failure occurs
Go to a specific ICM valve opening degree
• Hermetic magnetic motor
• Enclosure: IP67 ~ NEMA 6
• Approvals: CE, UL, CRN
• Connectors for easy installation and servicing
• ICAD 600A / 1200A ensures an acurate
feedback on the valve position.