Brand Name: TAQU
Model Number: T53
Place of Origin: China
Summary
T53 series water pipe temperature sensor can be used for temperature measurement of various air conditioning water systems and refrigerants. There are a variety of probe length structures to choose from. In order to facilitate field installation and protect sensor components and sensors from being eroded by the tested liquid, special liquids should be used in conjunction with corresponding bushing. The product uses a high performance built-in linear processor and has a variety of output signals. It is specially applied to temperature measurement equipment in HVAC pipeline system.
T53 series water pipe temperature sensor, probe diameter is 6.4mm, there are a variety of lengths to choose. T53 series water pipe temperature sensor sleeves are used together. The sleeve specifications can be configured according to the requirements of probe and pipeline.
Features
- High Precision Temperature Sensor
- Applicable to all kinds of intelligent building environment monitoring, HVAC system
- Advanced circuit design, high measurement accuracy
- Stable performance and good linearity
- Easy to install, cost-effective
- Multiple output modes are optional
- Calibration of Sensor Exit Standard
Application
- HVAC
- Electronic Workshop
- Environmental Monitoring in Computer Room
- Power Environment Monitoring
- Agricultural Environmental Monitoring
- Meteorological Environmental Monitoring
- Environmental monitoring of biopharmaceuticals
- Airports, subway stations, hotels, museums, gymnasiums, etc.
Parameter
Temperature |
Accuracy: Range: Stabilization Time: Calibration: |
±0.2℃、±0.3℃、±0.5℃、±1℃ 0~50℃、0~80℃、-5~60℃ Refer to the Selection Table 2-5mins Standard calibration |
Output parameter |
Signal output: |
4~20mA RL<400 ohm 0~10VDC RL>10k ohm Refer to the Selection Table for details. |
485 Parameter |
Signal type: RS485 type: Connect: Address: Protocol: Data Format: Baud Rate: |
RS485 Serial Port Output Multipoint, Half Duplex 2Wire system, maximum communication distance 1200 meters, terminal direct connection 1-254 Through the switch/software settings, the broadcast address is: 0, and the default address is: 1 MODBUS 1Start bits, 8 data bits, no parity, 2 termination bits 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 19200 bit/s, 28800 bit/s, 38400 bit/s, through the switch/software settings, the default value is 9600 bit/s. |
Power |
Power supply: |
Current-mode 24VDC±10% Voltage-mode 24VDC/AC±10% RS485 10~28VDC |
Connection mode |
Terminal: Cable specifications: |
5.0mm spacing, M3 steel screw, 0.2Nm torque, 0.02 ohmic contact resistance. 24~18AWG(0.2~1.0mm2) ,stripping length 6-7mm |
Environment |
Working environment: |
Temperature -20~70℃ probe up to 110℃ Humidity 0~99%RH,no condensation |
Storage environment: |
Temperature -30~80℃ Humidity 0~95%RH,no condensation |
|
Protection level |
Shell: EMC: |
IP65 Reference IEC 529 – 598/GB 700 – 86/ GB 4208 Reference GB/T 13926,EN61000-6-2,EN61000-6-3 |
Accessories |
Casing Material: insertion depth: Thread : |
304Stainless Steel 50-350mm M22×1.5/G1/2”/1/2-NPT |
Material and Color |
Shell: Probe: Probe Length: Weight: |
ABS(Black/Light Blue) 304 Stainless Steel Configure according to the length of casing. 300g(total weight) |
Ordering Information
Series |
Temperature Sensitive Component |
Temperature Range |
||||
T53- |
PT100A PT100B PT1000A PT1000B A/CP(10KΩ, TypeⅡ) A/AN(10KΩ, Type Ⅲ) 10K Type L NTC15K A/20K(20KΩ) Resistance output only |
(A) (B) (C) (D) (E2) (E3) (E) (F) (G) |
Sensitive component 0~50℃ 0~80℃ 0~100℃ -5~60℃ -20~80℃ -40~80℃ -50~50℃ -50~100℃ |
(T0) (T1) (T2) (T3) (T4) (T5) (T6) (T7) (T8) |
-20~40℃ -20~60℃ -10~110℃ -20~100℃ -30~70℃ -40~60℃ Custom |
(T15) (T16) (T17) (T19) (T20) (T21) (UD) |
Temperature Accuracy |
Signal Output |
Sleeve Insertion depth |
|||
±0.2℃ ±0.3℃ ±0.5℃ ±1℃ |
(B) (C) (D) (E) |
4~20mA 2-wire 0~5VDC 0~10VDC RS485 Output |
(2) (4) (5) (RS) |
50mm 100mm 150mm 200mm 250mm 300mm 350mm 700mm |
(T05) (T10) (T15) (T20) (T25) (T30) (T35)(T70) |