Brand Name: zhongke
Model Number: Fan coil series
Place of Origin: shandong
Product features
1, fine structure, beautiful shape
Product structures are all made of high quality galvanized steel, sound-absorbing insulation material selection, configuration before curved blade type wind wheel, a window type aluminum finned coil and galvanized anti-corrosion insulation water pans, etc.
2, design features
Wind wheel, low speed, small volume, light weight, good strength and can be easily arranged at any place.
3, high efficiency
Coil with high quality copper tube and aluminum window type radiator fin, the mechanical tube to ensure fin closely contact with copper pipe, the best effect, products rigid inspection before they go out, and through the pressure test of leakage (leakage test pressure of 2.4 kg/cm2), to ensure product quality and performance.
4, less water loss
Set head made from brass forging, uniform flow smoothly and set knob type exhaust valve outlet, can discharge the air inside the machine conveniently.
5, electricity, low noise, long service life
To adopt new technology research and production of special fan motor, shaft after quenched and tempered and hard chromium special treatment, the shaft never deformation, does not rust. USES the high quality oil bearing, it can automatic lubrication, without refueling, turns low noise, low input power. Configuration of galvanized wind turbines, classics of dynamic and static balance adjustment, with beautiful, air distribution effect is good, low noise, the service life of more than ten years. The overall noise is lower than the national standard.
Unit 6, performance parameters of the table
Remark:
1, cooling: used for water temperature 7 ℃ / 12 ℃; Return air condition: 27 ℃ dry bulb temperature, wet bulb temperature of 19.5 ℃.
2, heat supply, water supply temperature 60 ℃, water supply and cooling condition of the same; Return air condition: dry bulb temperature of 21 ℃;
In the table 3, the noise in the background noise of 16.5 dB (A) to the dead room closed;
4, low static pressure unit with tuyere and filter, static pressure value is 0 pa; Without tuyere and filter, static pressure value is 12 pa;
5, according to customer requirements to do other static pressure units (in when signing a contract to be marked).