Brand Name: SANHENG
Model Number: SHP-606
Place of Origin: Zhejiang, China (Mainland)
Dual Pressure Switch with Micro Switch Structure for Refrigeration of SHP 606
Features
For use with fluorinated refrigerants as well as with air, liquid, oil
Allowable fluid temp: -45℃~+120℃
Concentrate pressure control of low pressure side and over-pressure protection of high pressure side into one
Beside auto reset, high pressure manual reset and high & low pressure are also available
Flexible mounting plate suits various kind applications
Ambient temperature:-20℃~70℃
Electrical Function
Rated Voltage (V) Rated Amps (A) |
Power Factor (cosφ) |
125V /250V AC |
|
Non-Inductive Current |
1 |
12 |
|
Inductive Current |
Full Load |
0.75 |
12 |
Instantaneous |
0.45 |
72 |
Specification
Model |
Pressure |
Adjustable Range (bar) |
Switch differential (bar) |
Factory Setting (bar) |
Max. Working Pressure(bar) |
|||
Min |
Max |
Min |
Max |
OFF |
ON |
|||
SHP-306 |
Low |
-0. 5 |
6 |
0. 6 |
4 |
3 |
2 |
16 |
High |
8 |
30 |
Fixed 3-5 |
20 |
15 |
33 |
||
SHP-306HM |
Low |
-0. 5 |
6 |
0. 6 |
4 |
3 |
2 |
16 |
High |
8 |
30 |
≤4 |
20 |
Manual Reset |
33 |
||
SHP-606 |
Low |
-0. 5 |
6 |
0. 6 |
4 |
3 |
2 |
16 |
High |
8 |
30 |
Fixed 3-5 |
20 |
15 |
33 |
||
SHP-606HM |
Low |
-0. 5 |
6 |
0. 6 |
4 |
3 |
2 |
16 |
High |
8 |
30 |
≤4 |
2.0 |
Manual Reset |
33 |
||
SHP-606HLM |
Low |
-0. 5 |
6 |
≤2 |
3 |
Manual Reset |
16 |
|
High |
8 |
30 |
≤4 |
2.0 |
Manual Reset |
33 |
v Pay by T/T, LC
v Customers can choose which payment ways that you accept, paypal is most useful and safe, please don’t refusepaypal fee when you choose it.
v Loading Port: ShangHai or NingBo, China
v Samples are available within 7-10 working days.
v Mass Production Delivery: 20 -50days after sample confirmation