Brand Name: GDNESIS
Model Number: 800F
Place of Origin: CHINA
Fresh Air System Controller Instruction
KF-800F
Description
New Air intelligent controller (KF-800F) can monitor real-time indoor temperature, CO2 concentration. Controller output signal can directly control the startup and speed of fan. It can be widely used in residential, commercial and industrial applications, and can effectively improve air quality, create a healthy, comfortable, energy-efficient living and working environment.
Buttons Function
: Setting Time Button
: Up Button
: Down Button
:Setting Working Mode(Auto-→MANUAL→TIMER)
LCD Display:
Instruction
1. AUTO Mode: CO2 concentration<500ppm, Fan is in LOW Speed. 500ppm<CO2 concentration<799ppm, Fan is in Med Speed. 800ppm<CO2 concentration, Fan is in HIGH Speed
2. MANUAL Mode: Setting the fan as OFF, LOW, MED,HIGH by button and
. In MANUAL MODE,the fan will run according to the setting, wont be affacted by CO2 concentration.
3. PROGRAMMING Mode: Programming mode: Controlller will be run according to the set time & speed(7 days, 4 time periods each day).
4. Programming Setting: Long press button for 2 second and then enter setting parameter interface. Firstly, local time calibration. Press
button to change Week / Hour / Minute,and the corresponding parameter will flash.Press
and
button to adjust the value. After finsh Local time calibration, go on press
button enter first period hour setting on Monday, press
button change to Hour, Minute,Fan Speed and press
and
button adjust value. After done first period, press
button enter second period hour setting on Monday...Repeat above steps to set all 28 time periods.Controller will be return to normal working mode and save setting Parameter automatically If there is no any operation for the buttons for 10 seconds during the setting process.
5. Backlight: CO2 concentration<500ppm, backlight is Green,
500ppm<CO2 concentration<799ppm,backlight is Yellow, 800ppm<CO2 concentration backlight is Red
6. RS485 is Option. Standard Communication Protocol
Parameter
CO2 display range: 350ppm-3000ppm
CO2 adjustment range: 350ppm-1500ppm
Dimension::86×86×40mm
Pre-heattime: 1 minute
hole distance:60mm(standard)
Response time: ≤10 seconds
Recovery time: ≤30 seconds
Power supply: 200~240VAC,50Hz-60Hz
Working Temp.: -10-50℃
Power:≤0.5W Humidity range: 5~99%RH
Control power:≤200W
Storage temperature: -10° c- +60° c
Output interface: Three-speed Fan
Storage humidity: ≤ 60% RH
Temperature display range: 0-50° c
Life: ≥10 years
Wiring Diagram