Brand Name: Techco
Model Number: 2HP TO 200HP
Place of Origin: CHINA
Air-cooled Condensing Unit For Chiller (3HP - 15HP)
Air-cooled Condensing Unit for Chiller with High Temperature 0C (3HP - 15HP)
Copeland ZB/ZSI/ZR Series and Danfoss full hermetic scroll compressor air-cooled Condensing Unit.
Unit includes liquid tank,dry filter,danfoss solenoid valve,liquid sight glass,H/L pressure gauge and pressure control. External rotor low noisy fan.
Refrigerant: R404A/R134a/R507/R22
Voltage: 380V/3/50HZ
220V/1/50HZ
460V/3/60HZ
220V/3/60HZ
Air-cooled Condersing Unit Chiller 3HP - 15HP Technical Parameter Selection Sheet:
Copeland Compressor Scroll Compressor Full Hermetic Compressor High Temperature Air-cool Condersing Unit:+10C to -15C
Model of units |
GXW3CQFZG |
GXW5CQFZG |
GXW10CQFG |
GXW7CQFZG |
||
Power |
3HP |
5HP |
10HP |
15HP |
||
Applicable Temperature(℃) |
+10℃ To -15℃ |
|||||
Refirgerant |
R404A |
|||||
Power Supply |
380V/3/50HZ |
|||||
Condenser |
Quantity of Fan(piece) |
1 |
2 |
2 |
2 |
|
Air volume(m³/h) |
1x3200 |
2x3200 |
2x6570 |
2x8720 |
||
Power of Fan(W) |
1x60 |
2x60 |
2x450 |
2x600 |
||
Refrigerating capacity of compressor units |
Evaporating Temperature +5℃ |
Cooling capacity |
7910 |
12250 |
28300 |
37300 |
Power |
3020 |
5440 |
9550 |
15850 |
||
Evaporating Temperature -5℃ |
Cooling capacity |
4930 |
8230 |
20700 |
27500 |
|
Power |
3180 |
5400 |
8840 |
14450 |
||
Evaporating Temperature -12℃ |
Cooling capacity |
3960 |
6600 |
16150 |
21400 |
|
Power |
2980 |
5040 |
8410 |
13650 |
||
Coupling |
Tube couping |
3/8 |
1/2 |
5/8 |
5/8 |
|
Suction coupling |
5/8 |
3/4 |
1-3/8 |
1-3/8 |
||
Overall dimensions |
(L)mm Length |
970 |
980 |
1330 |
1730 |
|
(B)mm Width |
410 |
410 |
900 |
1000 |
||
(H)mm Height |
835 |
1330 |
900 |
1000 |
||
Mounting dimensions |
(D)mm Length |
625 |
625 |
900 |
1300 |
|
(E)mm Width |
380 |
380 |
940 |
1020 |
||
Standard configuration of units:compressor,conderser,liquid receiver,pressure controller,pressure gauge,filter,solencid Valve and wirring box,etc. |
Note:
1.Cooling capacity in the form is calculated when the ambient temperature is 32℃.
2.Configuration can be added according to customers’ requirements.
3.When the compressor uses refrigerant R404A,and evaporating temperature lower than -20℃
4.Air-cooled Condersing Unit Chiller 3-15HP
5.High Temperature Air-cool Condersing Unit:+10C to -15C