Brand Name: Clitech
Model Number: CAM-12XB
Place of Origin: Guangdong, China (Mainland)
Technical Parameters:
Website:www.clitechchina.en.alibaba.com
Word: Heat pump all in one
Model | CAM-12XB | CAM-16XB | CAM-20XB | |
AC cooling | Cooling capacity kW | 7.44 | 9.8 | 12.4 |
AC Water flow M³/H | 1.28 | 1.68 | 2.13 | |
Input power KW | 2.58 | 3.4 | 4.3 | |
Rated input current A | 11.87 | 16.5 | 7.6 | |
EER | 2.88 | 2.88 | 2.88 | |
AC cooling with heat recovery for hot water | Cooling capacity kW | 7.8 | 10 | 13 |
AC Water flow M³/H | 1.34 | 1.72 | 2.24 | |
Heating capacity kW | 10.5 | 14.5 | 16.5 | |
Hot water output T/H | 0.22 | 0.27 | 0.35 | |
Input power KW | 2.3 | 3.1 | 3.7 | |
Rated input current A | 10.59 | 16.2 | 7.1 | |
EER+COP | 7.96 | 7.88 | 7.97 | |
AC heating with Hot water | Heating capacity kW | 11 | 14.8 | 19.00 |
Hot water output T/H | 0.24 | 0.32 | 0.41 | |
Input power KW | 2.44 | 3.2 | 4.07 | |
Rated input current A | 11.23 | 16 | 7.76 | |
COP | 4.51 | 4.62 | 4.67 | |
Rated & Max water temp °C | 55°C and 60°C | |||
Power source V/PH/HZ | 220V/1N/50HZ or 380V/3N/50HZ | 380V/3N/50HZ | ||
Noise level dB(A) | <50 | <54 | <55 | |
Unit size W x D x H mm | 710*710*810 | 810*780*1050 | 810*780*1050 | |
Wood Packing W x D x H mm | 810*810*980 | 910*880*1220 | 910*880*1220 | |
Net weight Kg | 110 | 165 | 175 | |
Throttle Type | Electronic expansion valve/Thermal expansion valve | |||
Refrigerant Qty kg | 3.2 | 4.8 | 5.2 | |
Sanyo Compressor Pcs | 1 | 1 | 1 | |
Protection | Built-in protection as overheating protection, sequence protection, undervoltage protection, time-delay start protection etc | |||
Condensor | Heat exchanger type | Finned tube heat exchanger | ||
Qty pcs | 1 | 1 | 1 | |
Fan type | Axial big twist angle fan | |||
Motor KW | 0.2 | 0.3 | 0.3 | |
Hot water | Heat exchanger type | Efficient tube in tube heat exchanger with Max working pressure 1000 kPa | ||
Qty pcs | 1 | 1 | 1 | |
Water flow M³/H | 1.89 | 2.45 | 3.27 | |
Pressure Loss KPa | 27 | 30 | 32 | |
Pipe size mm | 20 | 25 | 25 | |
Air Conditioner | Heat exchanger type | Efficient tube in tube heat exchanger | ||
Quantity | 1 | 1 | 1 | |
water flow M³/H | 1.34 | 1.68 | 2.24 | |
Pressure Loss Kpa | 12 | 13 | 13 | |
Pipe size mm | 20 | 25 | 25 | |
Water side max working temp kPa | 1000 | 1000 | 1000 | |
1.Rated cooling working condition: Air source side inlet water temp is 35°C, AC side inlet water temp is 12°C, outlet water temp is 7°C | ||||
2.Rated heating&hot water condition: Air source side DB/WB is 20°C/15°C,initial hot water temp 15°C, ending hot water temp 55°C;AC side inlet water temp 40°C,outlet water temp 45°C. | ||||
3.Rated cooling&hot water working condition: initial hot water temp 15°C,ending hot water temp 55°C;AC side inlet water temp 12°C,outlet water temp 7°C. |
This CAM series Air to water heat pump Heating Cooling and Hot water unit can connect to indoor fan coil unit for house cooling in summer and house heating in winter; sanitary hot water produced all year around.
More models of heat pump all in one series: