Brand Name: WINNER
Model Number: SW-B152
Place of Origin: China
Winner spring-return zone valve SW-BBSP series have compact structure, stable operation, excellent capacity of water stoppage, large water flow rate, zero dirt block and low torque. Winner spring-return zone valves are widely used in fan coil units, cooling/ heating system and HVAC system.
Application
Fan coil units, cooling/ heating system and HVAC system.
Operational mode
Winner spring-return zone valve is motor-operated by on/off type actuator. The actuator adopts totally
closed unidirectional hysteresis synchronous motor, having waterproof design and spring automatic reset
function
Valve body:
Medium: cold/hot water, with 50% glycol Temperature of medium: 0 to 93℃
Rated pressure: PN20 Pipe connector: internal thread
Ambient temp. range: 0 to 40℃; Size: 1/2’’, 3/4’’ and 1’’
Valve type: 2-way and 3-way
Actuator:
Working voltage: 24VAC, 110/120VAC, 230VAC; 50/60H z.
On/off time: 13-18s, Spring return time: 4-5s
Motor power: 6.5W, 7 VA
Material
Valve body: forged brass Valve seat: brass
Valve stem: chrome-plated brass
Actuator shell: aluminum; Actuator bottom case: stainless steel.
Specification
Model No. |
Size |
Description |
Kv(Cv) |
Closing pressure |
Weight (g) |
SW-B152 |
15MM (1/2’’) |
2 way valve |
2.2(2.5) |
0.18MPa (25PSI) |
700 |
SW-B202 |
20MM (3/4’’) |
3.0(3.5) |
0.16MPa (23PSI) |
850 |
|
SW-B252 |
25MM (1’’) |
6.9(8.0) |
0.14MPa (20PSI) |
1000 |
|
SW-B153 |
15MM (1/2’’) |
3 way valve |
2.6(3.0) |
0.18MPa (25PSI) |
750 |
SW-B203 |
20MM (3/4’’) |
3.4(4.0) |
0.16MPa (23PSI) |
900 |
|
SW-B253 |
25MM (1’’) |
6.5(7.5) |
0.14MPa (20PSI) |
1050 |
|
SW-B152H |
15MM (1/2’’) |
High C.P 2 way valve |
1.7(2.0) |
0.45MPa (65PSI) |
700 |
SW-B202H |
20MM (3/4’’) |
2.2(2.5) |
0.35MPa (50PSI) |
850 |
|
SW-B252H |
25MM (1’’) |
3.0(3.5) |
0.20MPa (30PSI) |
1000 |
|
SW-B153H |
15MM (1/2’’) |
High C.P 3 way valve |
1.7(2.0) |
0.45MPa (65PSI) |
750 |
SW-B203H |
20MM (3/4’’) |
2.6(3.0) |
0.35MPa (50PSI) |
900 |
|
SW-B253H |
25MM (1’’) |
3.4(4.0) |
0.20MPa (30PSI) |
1050 |
Installation:
The valve body should be installed in fan coil or in the radiator first, then you can install the actuator.
The actuator and valve body can be connected directly, fast and easy installation, without using any connection and calibration tools.